SCHEMATIC OF LIQUID LEVEL SENSOR
Reading, Drawing, and Interpreting Liquid Level Sensor Schematics
A practical guide for engineers, technicians, and designers working with level measurement and control systems
Introduction
What a Liquid Level Sensor Schematic Shows
1. The Sensing Element
2. The Signal Path
3. Power and Ground
●Supply voltage and current draw
●Output signal type (dry contact, NPN, PNP, 4-20 mA, 0-10 V, RS-485, IO-Link)
●Wire colours or terminal designations
●Any intrinsic safety parameters (for hazardous-area sensors)
●Failure mode (NO / NC) for switch-type sensors
Float Switch: Schematic and Wiring
Circuit Schematic
Symbol:
[==== Float body ====] <- buoyant, rises/falls with liquid surface
|
[Magnet - permanent]
|
+------------------------+
| Glass envelope |
| [Blade A] [Blade B] | <- reed switch contacts
+------------------------+
| |
Wire 1 Wire 2
Key Components
Float body Schematic symbol / key components
Buoyant shell Hollow shell made of PP, NBR, or SS316L. Rises and falls with liquid surface.
Permanent magnet Sealed inside the float. Field strength determines switch pull-in and drop-out points.
Reed switch Two ferromagnetic contacts sealed in a glass tube. The magnet pulls contacts together when float is at the setpoint.
Stem / lead wires Two wires exit the stem - one to each reed contact. No polarity. No power required at the switch itself.
Wiring Configurations
Two-wire switching (simple pump control):
AC/DC Supply (+V) ----+------- Wire 1 ----+--[Reed]--+-- Wire 2 ---+-- Pump/Motor -- Ground
NO contact (pump on when tank full):
Supply + ---- Wire 1 ---- [Float: NO contact] ---- Wire 2 ---- Relay coil ---- Ground
NC contact (fail-safe alarm when float falls):
Supply + ---- Wire 1 ---- [Float: NC contact] ---- Wire 2 ---- Alarm relay ---- Ground
Important Schematic Notes
●The reed switch rating (typically 0.5-2 A, 100 V AC/DC) is much lower than motor inrush current - always drive a relay or contactor, never the pump motor directly
●For a dual-pump control circuit with a high and low setpoint, two float switches are wired in series (low-level = stop, high-level = alarm)
●In a three-wire SPDT configuration, Wire 1 and Wire 2 are the common; a third wire (Wire 3) is the alternate contact
Conductivity Probe: Schematic and Wiring
Circuit Schematic
Symbol:
Electrode A --------------------+
|
+---------+
| Sensing | <- AC source, 5-12 V, 50-60 Hz
| Circuit | (AC prevents electrolysis)
+---------+
|
Electrode B --------------------+
Tank wall (grounded) ---------+
Key Components
Electrode probe Schematic symbol / key components
Electrode A (signal) One or more rods at the setpoint height. Material: SS316L, Hastelloy C, or titanium.
Electrode B (return) Same material as Electrode A. Can be a second rod or the grounded tank wall.
AC sensing circuit Low-voltage AC source (5-12 V, 50-60 Hz). Detects current flow when both electrodes are submerged.
Relay / controller output When current is detected, the circuit energises a relay coil. Output: NO or NC dry contact to PLC.
Wiring to a PLC or Controller
Typical industrial wiring:
Probe Electrode A -----> to controller input terminal
Probe Electrode B -----> to controller ground / reference
Controller output -----> PLC digital input (24 V DC signal)
Supply: 24 V DC to controller (probe needs no separate power)
Important Schematic Notes
●Always use AC excitation - DC will cause electrolysis and electrode corrosion within days
●Minimum liquid conductivity: approximately 20 µS/cm. Pure water (~1 µS/cm) will not work - choose a different technology
●In tanks with non-conductive walls (plastic), use a third reference electrode touching the tank floor
●The schematic should show the AC waveform symbol - if it shows DC, the probe will fail quickly
Optical TIR Sensor: Schematic and Wiring
Circuit Schematic (Functional Block Diagram)
Block diagram:
+-------------------------------------------------------+
| Optical TIR Sensor |
| |
| IR LED ----> [Prism] ----> Phototransistor |
| (source) TIR in air (detector) |
| | | | |
| Current Refractive Collector |
| driver index current |
+-------------------------------------------------------+
| |
+24 V DC Signal output
(or 5-24 V depending on model) NPN / PNP / IO-Link
Key Components
Optical sensing head Schematic symbol / key components
IR LED Infrared emitter, typically 850-940 nm wavelength. Requires a current-limiting resistor or constant-current driver.
Prism (TIR element) Glass or polysulfone tip. In air: TIR traps light inside. In liquid: TIR breaks, light escapes.
Phototransistor Detector that produces a collector current proportional to received light. High current in air, low in liquid.
Signal conditioning Comparator circuit: compares phototransistor output to a voltage threshold. Outputs ON or OFF.
Output stage NPN (sinks current to ground), PNP (sources current from supply), or IO-Link digital output.
NPN vs PNP Wiring
NPN output (sinking) - most common in Asia and Europe:
Load
[+]---[ ]---[ Signal ]---[ PLC input ]
|
NPN collector
|
PLC ground (GND)
PNP output (sourcing):
PLC supply (+24 V)
|
[ PLC input ]---[ Signal ]---[ PNP collector ]
|
Load
|
PLC ground
Important Schematic Notes
●The schematic must show the LED current-limiting resistor - without it, the LED will burn out within hours
●IO-Link sensors use a three-wire connection: pin 1 = supply, pin 3 = ground, pin 4 = signal/data
●TIR sensors are polarity-sensitive - the LED has an anode and cathode; the phototransistor has an emitter and collector
●For hazardous locations, the schematic will show an intrinsically safe (Ex ia) barrier between the sensor and the controller
Ultrasonic Sensor: Schematic and Wiring
Circuit Schematic (Block Diagram)
Block diagram:
+------------------------------------------------------------+
| Ultrasonic Level Sensor |
| |
| Piezoelectric ToF Signal Output |
| transducer processor conditioning stage |
| [sends pulse] [measures t] [filters] [4-20mA/RS485] |
| | | |
+------------------------------------------------------------+
| |
Temperature sensor 4-20 mA / 0-10 V
(for speed-of-sound compensation) RS-485 / IO-Link
| |
Built-in |
+24 V DC supply
Key Components
Ultrasonic sensor Schematic symbol / key components
Piezoelectric transducer Both sends and receives. Fires a burst of pulses at 40-200 kHz, then listens for the echo.
Temperature sensor Built into most industrial sensors. Measures air temperature to compensate for changes in speed of sound.
ToF processor Measures the round-trip travel time. Calculates distance: D = (c x t) / 2.
Signal conditioning Filters out noise and multipath echoes. Determines the true echo from the liquid surface.
Output stage 4-20 mA current loop (two-wire, loop powered), 0-10 V voltage, RS-485/Modbus, or IO-Link.
Two-Wire 4-20 mA Wiring
Standard loop wiring:
+24 V DC supply
|
+----[ Sensor + ]----[ Sensor - ]----+----[ PLC 4-20 mA input ]----+
| (loop power + signal on | |
| same two wires) +---[ PLC ground ]-------------+
Important Schematic Notes
●Two-wire 4-20 mA sensors carry both power and signal on the same pair of wires - the PLC must be configured as a current source
●The schematic should show the temperature compensation block - this is what separates an industrial ultrasonic sensor from a cheap HC-SR04 module
●RS-485/Modbus sensors require a twisted pair cable (A/B signal) plus a separate power pair - typically four wires total
●For analog output sensors, the wiring diagram should show the minimum load resistance (typically 250-500 ohms for 4-20 mA)
Hydrostatic Pressure Sensor: Schematic and Wiring
Circuit Schematic (Block Diagram)
Block diagram:
+------------------------------------------------------------+
| Hydrostatic Pressure Sensor |
| |
| Diaphragm ---- Amplifier ---- Signal ---- Output |
| (strain (instrumentation conditioning stage |
| gauge) amplifier) |
| | | |
| Vented tube (atmospheric reference) 4-20 mA / 0-10 V
+------------------------------------------------------------+
| |
Submersed in liquid +24 V DC supply
Key Components
Pressure sensor Schematic symbol / key components
Diaphragm Thin metal or ceramic membrane. Deflects under pressure from the liquid column above it.
Strain gauge / capacitive element Converts diaphragm deflection to an electrical signal (resistance or capacitance change).
Instrumentation amplifier Amplifies the small sensor signal and removes common-mode noise.
Vented tube A separate passage inside the cable connects the sensor's rear cavity to atmospheric air. Critical: this is the reference for ambient pressure.
Output stage Two-wire 4-20 mA, three-wire 0-10 V, or four-wire with separate excitation and signal outputs.
Two-Wire 4-20 mA Wiring (Same as Ultrasonic)
Loop wiring:
+24 V DC supply
|
+----[ Sensor + ]----[ Sensor - ]----+----[ PLC 4-20 mA input ]----+
| | |
| +---[ PLC ground ]-------------+
Critical - vent tube routing:
Sensor vent tube: must route continuously upward from sensor to exit above the highest
water level. The tube opening must remain dry and unobstructed. Moisture inside
the vent tube causes zero drift or complete failure.
Important Schematic Notes
●The vent tube is shown in the schematic as a separate passage from the signal wires - never seal or pinch it
●For vented sensors, the schematic shows two pressure connections to the electronics: the front (process pressure) and the rear (atmospheric reference via the vent tube)
●Submersible versions have the electronics sealed in epoxy inside the probe body - the schematic shows IP68 rated housing
●For non-vented (sealed) sensors used in sealed tanks, the sensor measures absolute pressure - the schematic must show the reference vacuum chamber inside the sensor
Radar Level Sensor: Schematic and Wiring
Circuit Schematic (Block Diagram)
Block diagram:
+------------------------------------------------------------+
| Radar Level Sensor |
| |
| Horn / Rod Mixer / ToF / Output |
| Antenna <--- FMCW IC processor stage |
| (sends & (calculates |
| receives) distance) |
| | | |
+------------------------------------------------------------+
| |
+24 V DC or 230 V AC (mains powered)
Output: 4-20 mA / HART / RS-485 / IO-Link
Key Components
Radar sensor Schematic symbol / key components
Antenna (horn or rod) Directs the microwave beam toward the liquid surface and collects the reflected echo.
Microwave source (VCO) Voltage-controlled oscillator. In FMCW sensors, sweeps frequency over time. In pulsed sensors, fires short microwave bursts.
Mixer / IF stage In FMCW: mixes transmitted and received signals to produce a beat frequency proportional to distance.
DSP / processor Analyses the echo in frequency domain (FMCW) or time domain (pulsed). Calculates level from travel time.
Power supply + output Mains-powered sensors (230 V AC) are common for industrial radar. Output: 4-20 mA, HART, RS-485, or IO-Link.
Wiring - 4-20 mA with HART
Four-wire (separate power and signal):
Power: L + N (230 V AC) -----> sensor power terminals
Signal: + / - (4-20 mA + HART FSK) -----> PLC analog input + HART modem
Two-wire (loop powered with HART):
+24 V DC ----[ Sensor ]----[ PLC 4-20 mA + HART input ]---- GND
Important Schematic Notes
●Industrial radar sensors are typically mains-powered (230 V AC) - the schematic shows L/N/PE connections plus the signal output wiring
●HART protocol superimposes a 1.2 kHz / 2.2 kHz FSK signal on top of the 4-20 mA analog current - a HART modem connects in parallel with the PLC input
●The antenna type (horn, rod, parabolic) is shown on the schematic mechanical drawing - it affects the beam angle and is critical for installation planning
●For SIL-rated safety systems, the schematic shows a redundant (dual) 4-20 mA output
Capacitive Level Sensor: Schematic and Wiring
Circuit Schematic (Block Diagram)
Block diagram (insertion probe type):
+------------------------------------------------------------+
| Capacitive Level Sensor |
| |
| Electrode A <--- Oscillator ----> Comparator ----> Output |
| Electrode B (LC tank) (threshold) (NPN/PNP/4-20mA)|
| | | |
| Liquid as dielectric (air -> water changes C) |
+------------------------------------------------------------+
| |
+24 V DC supply
Key Components
Capacitive sensor Schematic symbol / key components
Electrode pair (probe) Two conductive rods or plates separated by a gap. The liquid fills the gap and acts as the dielectric.
Oscillator circuit (LC tank) An inductor and the probe capacitance form an LC resonant circuit. Frequency or amplitude changes as capacitance changes.
Comparator / threshold detector Compares oscillator output to a reference voltage. Triggers when the signal crosses the threshold (liquid at setpoint).
Output stage NPN/PNP for point-level switches. 4-20 mA for continuous transmitters. IO-Link for digital output.
Through-Wall Capacitive Sensor
Configuration:
Sensor pad (electrode pair) mounted on outside of tank wall
Outside: [==== Sensor pad ====]
| Electric field |
Tank wall: [ Non-conductive ] <- PE, PP, polycarbonate, glass
| penetrates wall |
Inside: [==== Water ========] <- liquid fills near-wall region
Important Schematic Notes
●The schematic shows the electrode geometry - rod type, plate type, or coaxial cable - which determines sensitivity and minimum detectable level change
●Through-wall sensors require a non-conductive tank wall - the schematic will note the maximum wall thickness (typically <= 10 mm)
●Calibration is shown on the schematic as a trim potentiometer or Teach button - the sensor must be calibrated with the actual tank and liquid installed
●For continuous capacitive transmitters, the schematic shows the 4-20 mA output connection, which is calibrated against the full tank height
How to Read Any Liquid Level Sensor Schematic
Step 1 - Identify the Output Type
Output Type Wires Needed Connection to PLC Notes
Dry contact (NO/NC) 2 wires PLC digital input + common ground Passive - needs no power at sensor
NPN (sinking) 3 wires: +, -, signal Signal sinks current to PLC ground Common in Asia / Europe
PNP (sourcing) 3 wires: +, -, signal Signal sources current from PLC supply Common in North America
4-20 mA (two-wire) 2 wires: + and - PLC analog input configured as current source Power + signal on same pair
0-10 V (three-wire) 3 wires: +, -, signal PLC analog input (voltage mode) Signal is voltage - susceptible to cable length
RS-485 / Modbus RTU 4 wires: +, -, +24 V, GND PLC serial port or Modbus gateway Requires twisted pair cable
IO-Link 4 wires: L+, L-, C/Q1, C/Q2 IO-Link master port Digital, bidirectional, diagnostic data
Step 2 - Check the Supply Voltage
●12-24 V DC - most two-wire and three-wire industrial sensors
●24 V DC - standard industrial control voltage
●230 V AC / 110 V AC - mains-powered industrial radar sensors and some controllers
●3.3-5 V DC - Arduino-compatible modules (HC-SR04, eTape, capacitive modules)
Step 3 - Identify the Failure Mode
●NO contact: circuit is open when liquid is below the setpoint. Closes (pump ON) when liquid rises to the float.
●NC contact: circuit is closed when liquid is below the setpoint. Opens (alarm/trouble) when liquid rises and forces the float up.
●In fail-safe systems, an NC contact wired to a de-energised relay means a power failure or broken wire triggers the alarm - the system fails to a safe state.
Step 4 - Look for Intrinsic Safety Markings
●Maximum output voltage (Uo or Voc)
●Maximum output current (Io or Isc)
●Maximum power (Po)
●Approved safety barrier or zener diode reference
Conclusion